Mechanical installation
3.3 Assembly
Figure 3-15
The hood is mounted to the cabinet roof using the original roof screws.
1. Remove the original roof screws and any crane transport assemblies.
2. Only for hoods of options M43 and M54 :
Use the provided sealing tape to attach the contact surfaces of the hood.
3. Mount the hood to the corners on the cabinet roof.
Fasten the hood using the original roof screws
4. Only for type A cabinets:
Also fasten the hood in the center of the cabinet using the two supplied self-tapping
screws
50
Mounting a hood
(tightening torque: 5 Nm for M5).
(tightening torque: 50 Nm for M12).