Converter cabinet units 110 kw - 400 kw
Hide thumbs Also See for Sinamics G120P:
Table of Contents

Advertisement

Figure 7-27
Conditions for activating/deactivating an uncontrolled motor
Controlling the activation and deactivation of motors
Use p2371 to determine the order of activation/deactivation for the individual external
motors.
Table 7- 34
Order of activation for external motors depending on setting in p2371
p2371
Significance
0
Cascade control deactivated
1
One motor can be activated
2
Two motors can be activated
3
Two motors can be activated
4
Three motors can be activated
5
Three motors can be activated
6
Three motors can be activated
7
Three motors can be activated
8
Three motors can be activated
Inverter cabinet units
Operating Instructions, 12/2014, A5E32923362A
Stage 1
Stage 2
Stage 3
---
M1
M1
M1+M2
M1
M2
M1+M2
M1
M1+M2
M1+M2+M3
M1
M3
M1+M3
M1
M2
M1+M2
M1
M1+M2
M3
M1
M2
M3
7.7 Application-specific functions
Stage 4
Stage 5
M1+M2+M3
M2+M3
M1+M2+M3
M1+M3
M1+M2+M3
M1+M3
M2+M3
Functions
Stage 6
M1+M2+M3
409