Mechanical installation

3.3 Assembly

3.3
Assembly
Danger to life if the general safety instructions and remaining risks are not carefully
observed
If the general safety instructions and remaining risks are not observed, accidents can occur
involving severe injuries or death.
• Observe the general safety instructions.
• When assessing the risk, take into account residual risks.
3.3.1

Mechanical installation: checklist

Use the following checklist to guide you through the mechanical installation procedure for the
cabinet unit. Read the "Safety instructions" section at the start of these Operating
Instructions before you start working on the device.
Note
Checking the checklist
Check the boxes in the "Available" column appropriately if the associated task/option applies
to the cabinet unit. In the same way, check the "Completed" column once you have finished
the installation procedure to confirm that the activities are complete.
Item
Activity
1
Check the shipping and handling monitors prior to assembly. Refer to "Mechanical
installation/Assembly/Preparatory steps/Shipping and handling monitors".
2
The ambient conditions must be permissible. See "Technical data/General technical
data".
The enclosed units must be firmly attached using the anchor points provided (see
"Mechanical Installation/Preparation").
The cooling air can flow unobstructed.
3
The minimum ceiling height (for unhindered air outlet) specified in the Operating
Instructions must be observed. The cooling air supply must be not be obstructed
(see "Mechanical installation/preparation").
4
Components that are supplied separately for transport reasons (e.g. air deflectors,
canopies or hoods) must be fitted (see "Mechanical installation/fitting of canopies for
IP20 degree of protection and type A" or "Mechanical installation/fitting of additional
canopies (option M21) or hoods (option M23, M43, M54)").
5
The clearance around an open door (escape route) specified in the applicable acci-
dent prevention guidelines must be observed.
36
WARNING
Available
Inverter cabinet units
Operating Instructions, 12/2014, A5E32923362A
Completed