Siemens Sinamics G120P Operating Instructions Manual page 249

Converter cabinet units 110 kw - 400 kw
Hide thumbs Also See for Sinamics G120P:
Table of Contents

Advertisement

Analog Value Objects
In-
Object name
stance
ID
AV0
OUTPUT FREQ_Hz
AV1
OUTPUT FREQ_PCT
AV2
OUTPUT SPEED
AV3
DC BUS VOLT
AV4
OUTPUT VOLT
AV5
CURRENT
AV6
TORQUE
AV7
POWER
AV8
DRIVE TEMP
AV9
MOTOR TEMP
AV10
KWH (NR)
AV12
INV RUN TIME (R)
AV13
INV Model
AV14
INV FW VER
AV15
INV POWER
AV16
RPM STPT 1
AV17
FREQ STPT PCT
AV18
ACT FAULT
AV19
PREV FAULT 1
AV20
PREV FAULT 2
AV21
PREV FAULT 3
AV22
PREV FAULT 4
AV25
Select Setpoint
Source
AV28
AO1 ACT
AV29
AO2 ACT
AV30
MIN SPEED
AV31
MAX FREQ
AV32
ACCEL TIME
AV33
DECEL TIME
AV34
CUR LIM
AV39
ACT WARN
AV40
PREV WARN 1
Inverter cabinet units
Operating Instructions, 12/2014, A5E32923362A
Description
Output frequency (Hz)
Output frequency (%)
Motor speed
DC-link voltage
Output voltage
Motor current
Motor torque
Motor power
Heat sink temperature
Measured or calculated motor
temperature
Cumulative inverter energy con-
sumption (cannot be reset!)
Motor's operating hours (is reset
by entering "0")
Code number of Power Module
Firmware version
Rated power of the inverter
Reference speed of the inverter
Setpoint 1 (when controlling via
BACnet)
Number of the fault due to be
dealt with
Number of the last fault
Number of the fault before last
Number of the fault third from last
Number of the fault fourth from
last
Command to select the setpoint
source
Signal from AO 1
Signal from AO 1
Minimum speed
Maximum speed
Ramp-up time
Ramp-down time
Current limit
Indication of a pending alarm
Indication of the last alarm
6.8 Communication via RS485
Unit
Range
Hz
inverter-dependent
%
inverter-dependent
RPM
inverter-dependent
V
inverter-dependent
V
inverter-dependent
A
inverter-dependent
Nm
inverter-dependent
kW
inverter-dependent
°C
inverter-dependent
°C
inverter-dependent
kWh
inverter-dependent
h
0 ... 4294967295
---
inverter-dependent
---
inverter-dependent
kW
inverter-dependent
RPM
6.0 ... 210000
%
-199.99 ... 199.99
---
inverter-dependent
---
inverter-dependent
---
inverter-dependent
---
inverter-dependent
---
inverter-dependent
---
0 ... 32767
mA
inverter-dependent
mA
inverter-dependent
RPM
0.000 – 19500.000
RPM
0.000 ... 210000.00
0
s
0.00 ... 999999.0
s
0.00 ... 999999.0
A
inverter-dependent
---
inverter-dependent
---
inverter-dependent
Operation
Access
Parameter
type
R
r0024
R
HIW
R
r0022
R
r0026
R
r0025
R
r0027
R
r0031
R
r0032
R
r0037
R
r0035
R
r0039
W
p0650
R
r0200
R
r0018
R
r0206
W
p2000
C
HSW
R
r0947[0]
R
r0947[1]
R
r0947[2]
R
r0947[3]
R
r0947[4]
W
p1000
R
r0774.0
R
r0774.1
W
p1080
W
p1082
W
p1120
W
p1121
R
p0640
R
r2110[0]
R
r2110[1]
249

Advertisement

Table of Contents
loading

Table of Contents