Operation
6.3 Communication via PROFINET
Procedure
Proceed as follows to load the GSDML of the inverter:
● Load the GSDML of the inverter into the PROFINET controller, i.e. into your controller.
You can load the GSDML of your inverter in two ways:
– You can find the GSDML of the SINAMICS inverter on the Internet
– The GSDML is saved in the inverter. If you insert the memory card in the inverter and
● Unpack the GSDML before you use the device file.
6.3.4

Select telegram

The following telegrams are available:
Parameter
p0015
p0922
Precondition
In the basic commissioning, you have selected a setting with fieldbus.
See also Section: Commissioning (Page 123).
Procedure
Proceed as follows to set a specific telegram in the inverter:
● Use STARTER or the IOP to set parameter p0922 to the appropriate value.
180
(http://support.automation.siemens.com/WW/view/en/22339653/133100).
set p0804 = 12 , the GSDML will be written to the /SIEMENS/SINAMICS/DATA/CFG
folder on the memory card as a compressed file (PNGSD.ZIP).
Description
Macro drive unit
Configure the interface in the basic commissioning, and select a telegram.
PROFIdrive telegram selection
Set the send and receive telegram, also see Cyclic communication (Page 186)
1:
Standard telegram 1, PZD-2/2 (factory setting)
20:
Standard telegram 20, PZD-2/6
350:
SIEMENS telegram 350, PZD-4/4
352
SIEMENS telegram 352, PZD-6/6
353:
SIEMENS telegram 353, PZD-2/2, PKW-4/4
354:
SIEMENS telegram 354, PZD-6/6, PKW-4/4
999:
Free telegram configuring with BICO, see
Extend telegrams and change signal interconnection (Page 192)
Inverter cabinet units
Operating Instructions, 12/2014, A5E32923362A