7.4.5
Skip frequency bands
The inverter prevents continuous motor operation
at speeds in the suppression-speed range.
This can prevent speeds from being approached
stationary that, for example, cause excitation of
resonancy vibrations of the drive train.
To ensure that the speed does not constantly
increase and decrease in the suppression band-
width (speeds), the bands are assigned a hyste-
resis.
The suppression speeds apply in the positive and
negative direction of rotation.
Table 7- 18
Parameter
p1091
p1092
p1093
p1094
p1098
p1101
Inverter cabinet units
Operating Instructions, 12/2014, A5E32923362A
Setting skip frequency bands
Description
Suppression speed 1
Suppression speed 2
Suppression speed 3
Suppression speed 4
Suppression speed scaling
Suppression speed bandwidth
Functions
7.4 Setpoint calculation
351