Setting parameters for the temperature monitoring
Parameter
p0335
p0601
p0604
p0605
p0610
p0640
Additional information on the motor temperature monitoring can be found in function diagram
8016 of the List Manual.
Inverter cabinet units
Operating Instructions, 12/2014, A5E32923362A
Description
Specify the motor cooling
0: Natural cooling - with fan on the motor shaft (factory setting)
1: Forced ventilation - with a separately driven fan
2: Liquid cooling
128: No fan
Motor-temperature sensor type
0: No sensor (factory setting)
1: PTC (→ p0604)
2: KTY84 (→ p0604, p0605)
4: Temperature switch
Motor temperature alarm threshold (factory setting 130° C)
Motor temperature fault threshold (factory setting 145° C)
Setting for KTY84 sensor. The parameter has no significance for a PTC sensor.
Motor overtemperature response
Determines the response when the motor temperature reaches the alarm threshold
p0604.
0: Alarm (A07910), no fault.
1: Alarm (A07910); current limit is reduced and timer is started. Shutdown with fault
(F07011).
2: Alarm (A07910); timer is started. Shutdown with fault (F07011).
12: As for 2 but the last shutdown temperature is used to calculate the motor temper-
ature (factory setting).
Current limit (input in A)
Functions
7.6 Protection functions
367