Mapping the torque limit (p1520) with RPDO1
Procedure
Proceed as follows to accept the torque limit value in the communication:
1. Set the OV index for the torque limit:
first free OV index from the receive data from the "Free objects" 5800 table
2. Map the OV index for the torque limit with PZD2
– Set the COB-ID of RPDO1 to invalid:
– Link the mapping parameter object 2 of RPDO1 (p8710[1]) with the OV index for the
– Set the COB-ID of RPDO1 to valid:
r8750 shows which object is mapped to which PZD:
PZD2 (r8750[1]) = 5800 (torque limit)
3. Link the PZD receive word 2 in the receive word (p2050) with the torque limit:
p2050[1] = p1520[0]
Inverter cabinet units
Operating Instructions, 12/2014, A5E32923362A
p8700[0] = 80000232 hex
torque limit:
p8710[1] = 58000010 hex (5800 = OV index, 00 = fixed value, 10 ≙ 16-bit value)
p8700[0] = 40000232 hex
6.9 Communication over CANopen