Electrical installation
4.6 Power connections
Note
Information on the phase sequence
If the motor was connected with an incorrect direction of phase rotation, it can be corrected
without replacement of the phase sequence via p1820 (reverse output phase sequence).
With motors that can be star-connected or delta-connected, it must be ensured that the
windings are interconnected consistent with the operating voltage indicated on the type plate
or in the motor documentation. Make sure that the winding insulation of the connected motor
has sufficient insulation strength to meet the requirements for inverter operation.