Operation
6.2 Basic information about the drive system
Figure 6-3
Note
A connector input (CI) cannot be interconnected with any connector output (CO, signal
source). The same applies to the binector input (BI) and binector output (BO).
"Data type" in the parameter list provides information about the data type of the parameter
and the data type of the BICO parameter for each CI and BI parameter.
For CO and BO parameters, only the data type of the BICO parameter is given.
Notation:
• Data type BICO input: Data type parameter/Data type BICO parameter
Example: Unsigned32 / Integer16
• Data type BICO output: Data type BICO parameter
Example: FloatingPoint32
The possible interconnections between BICO input (signal sink) and BICO output (signal
source) are described in the List Manual in the table "Possible combinations for BICO
interconnections" in the section "Explanations on the parameter list".
The BICO parameter interconnection can be implemented in different data sets (CDS, DDS,
etc.). The different interconnections in the data sets are activated by switching the data sets.
176
Interconnecting signals using BICO technology
Inverter cabinet units
Operating Instructions, 12/2014, A5E32923362A