Changing Over Process Variables For The Technology Controller - Siemens Sinamics G120P Operating Instructions Manual

Converter cabinet units 110 kw - 400 kw
Hide thumbs Also See for Sinamics G120P:
Table of Contents

Advertisement

7.7.1.3

Changing over process variables for the technology controller

Note
We recommend that the units and reference values of the technology controller are
coordinated and harmonized with one another during commissioning.
Subsequent modification in the reference variable or the unit can result in incorrect
calculations or displays.
Note
Groups of units
For details concerning unit groups, please refer to the section titled "Unit group and unit
choice" in the List Manual.
SwitchIng over process variables of the technology controller
You change over the process variables of the technology controller using p0595. For
physical values, you define the reference variable in p0596.
Parameters affected by the unit switchover of the technology controller belong to unit group
9_1.
Switching the process variables of the additional technology controller 0
The process variables of the additional technology controller 0 switch over via p11026. You
define the reference variable for absolute units in p11027.
Parameters affected by the unit switchover of the additional technology controller 0 belong to
unit group 9_2.
Switching the process variables of the additional technology controller 1
The process variables of the additional technology controller 1 switch over via p11126. You
define the reference variable for absolute units in p11127.
Parameters affected by the unit switchover of the additional technology controller 1 belong to
unit group 9_3.
Switching the process variables of the additional technology controller 2
The process variables of the additional technology controller 2 switchover via p11226. You
define the reference variable for absolute units in p11227.
Parameters affected by the unit switchover of the additional technology controller 2 belong to
unit group 9_4.