Entering the motor data
During initial commissioning, you have to enter motor data using the operator panel. Use the
data shown on the motor type plate.
Figure 5-2
Table 5- 2
Motor data
System of units for line frequency and entering motor data
Motor:
Rated voltage

Rated current

Rated power

Rated power factor cos φ (only for motor data in kW)
Rated efficiency η (only for motor data in hp)
Rated frequency

Rated speed
Inverter cabinet units
Operating Instructions, 12/2014, A5E32923362A
Example of a motor type plate
5.3 Commissioning with the IOP
Parameter no.
Values
p0100
0
1
2
p0304
p0305
p0307
p0308
p0309
p0310
p0311
Commissioning
Unit
IEC [50 Hz / kW]
NEMA [60 Hz / hp]
NEMA [60 Hz / kW]
[V]
[A]
[kW] / [hp]
[%]
[Hz]
[min
] / [rpm]
-1
135