Siemens Sinamics G120P Operating Instructions Manual page 451

Converter cabinet units 110 kw - 400 kw
Hide thumbs Also See for Sinamics G120P:
Table of Contents

Advertisement

Number
Cause
F30035
Overtemperature, intake air
F30036
Overtemperature, inside area
F30037
Rectifier overtemperature
A30042
Fan has reached its maximum
number of operating hours
A30049
Internal fan defective
F30059
Internal fan defective
A30502
DC-link overvoltage
A30920
Temperature sensor fault
A50010
PROFINET name of station invalid
For further information, please refer to the List Manual.
Inverter cabinet units
Operating Instructions, 12/2014, A5E32923362A
Remedy
Check whether the fan is running.
Check the fan filter elements.
Check whether the ambient temperature is in the permissible range.
See F30035 and, in addition:
Check the motor load.
Check the line phases.
Replace the fan.
Reset the operating hours counter.
Check the internal fan and if required replace.
Check the internal fan and if required replace.
Check the unit supply voltage (p0210).
Check the dimensioning of the line reactor.
Check that the sensor is connected correctly.
Correct the name of station (p8920) and activate (p8925 = 2).
Alarms, faults and system messages
9.5 List of alarms and faults
451