Siemens Sinamics G120P Operating Instructions Manual page 141

Converter cabinet units 110 kw - 400 kw
Hide thumbs Also See for Sinamics G120P:
Table of Contents

Advertisement

25. A summary of all settings is displayed.
26. The final screen offers two options:
27. The successful saving of the settings is confirmed.
28. If the motor data identification has been activated, the
Inverter cabinet units
Operating Instructions, 12/2014, A5E32923362A
If the settings are correct, select "Next".
• Save
• Cancel the wizard
When "Save" is selected, the settings are saved in the
converter memory.
Function "Parameter saving mode" in "Menu" ⇒ "Ex-
tras" ⇒ "Parameter settings" is used to select the loca-
tion where the data is saved.
selected function will be started after the next ON
command.
Commissioning
5.3 Commissioning with the IOP
141