Operation

6.6 PROFIenergy profile for PROFINET

Error
Significance
value 1
86 hex
Write access only during commissioning of the data records (p0010 = 15) (operating state of the inverter pre-
vents a parameter change)
87 hex
Know-how protection active, access locked
C8 hex
Change request below the currently valid limit (change request to a value that lies within the "absolute" limits,
but is however below the currently valid lower limit)
C9 hex
Change request above the currently valid limit (example: a parameter value is too large for the inverter power)
CC hex
Change request not permitted (change is not permitted as the access code is not available)
Other application examples
See also: Reading and writing parameters acyclically
(http://support.automation.siemens.com/WW/view/en/29157692).
6.6
PROFIenergy profile for PROFINET
PROFIenergy is an energy management system for production plants, based on the
PROFINET communication protocol. The functionality is certified and described in the
PROFIenergy profile of the PNO.
The inverter supports the PROFIenergy profile V1.1 and the function unit class 3.
PROFIenergy functions of the inverter
The controller transfers the PROFIenergy commands in acyclic operation to the inverter in
data set 80A0 hex.
Parameters r5600 to p5614 are reserved for PROFIenergy functions in the inverter.
The PROFIenergy status is output in r5600.
The following commands and queries are available for the control:
PROFIenergy control commands
● Start_Pause
Switches from operating state S1 or S2 (start inhibit or start readiness) to energy-saving
mode.
Switches from energy-saving mode to the operating state.
● START_Pause_with_time_response
Switches from operating state S1 or S2 (start inhibit or start readiness) to energy-saving
mode and also specifies the transition times in the command response.
● End_Pause
Switches from energy-saving mode to the operating state.
Cancels the switching from the operating state to the energy-saving mode.