Summary of Contents for Siemens SINAMICS G120P

  • Page 3 ___________________ Safety information ___________________ General ___________________ SINAMICS Mechanical installation ___________________ Electrical installation SINAMICS G120P Output reactors ___________________ Technical specifications Operating Instructions Control version V4.7 05/2017 A5E32846921B AE...
  • Page 4 Note the following: WARNING Siemens products may only be used for the applications described in the catalog and in the relevant technical documentation. If products and components from other manufacturers are used, these must be recommended or approved by Siemens. Proper transport, storage, installation, assembly, commissioning, operation and maintenance are required to ensure that the products operate safely and without any problems.
  • Page 5: Table Of Contents

    Table of contents Safety information ........................... 7 Warnings ........................... 7 General ..............................9 Mechanical installation .......................... 13 Electrical installation..........................17 Technical specifications ........................19 Output reactors Operating Instructions, 05/2017, A5E32846921B AE...
  • Page 6 Table of contents Output reactors Operating Instructions, 05/2017, A5E32846921B AE...
  • Page 7: Safety Information

    Safety information Warnings WARNING Danger to life if the fundamental safety instructions and remaining risks are not carefully observed Non-compliance with the fundamental safety instructions and residual risks stated in Chapter 1 of the Installation Manual for PM330 Power Modules can result in accidents with severe injuries or death.
  • Page 8 Safety information 1.1 Warnings Note Support by SIEMENS service centers We recommend engaging the support and services of your local Siemens service center for all planning, installation, commissioning and maintenance work. Output reactors Operating Instructions, 05/2017, A5E32846921B AE...
  • Page 9: General

    When using components that have not been released, damage or malfunctions can occur at the devices or the system itself. • Only use output reactors that SIEMENS has approved for operation with SINAMICS. NOTICE Damage to the output reactor if the maximum pulse frequency is exceeded The maximum permissible pulse frequency when output reactors are used is 2.5 kHz or 4...
  • Page 10 General NOTICE Damage to the output reactor if it is not activated during commissioning The output reactor may be damaged if it is not activated during commissioning. • Activate the output reactor during commissioning via parameter p0230 = 1. Note Cable lengths Keep the connecting cables to the Power Module as short as possible (max.
  • Page 11 General Limiting the voltage rate of rise and voltage peaks using an output reactor and dv/dt filter Fast-switching IGBTs in the converter result in high voltage gradients dv/dt at the converter output. If long motor cables are used, this leads to an additional current load on the converter due to capacitive charge/discharge currents.
  • Page 12 General Output reactors Operating Instructions, 05/2017, A5E32846921B AE...
  • Page 13: Mechanical Installation

    Mechanical installation Dimension drawing Figure 3-1 Dimension drawing, output reactor Output reactors Operating Instructions, 05/2017, A5E32846921B AE...
  • Page 14 Mechanical installation Table 3- 1 Dimensions of the output reactor, Part 1 (all data in mm) 6SL3000- 2BE33-2AA0 2BE33-8AA0 2BE35-0AA0 2AE36-1AA0 2AE38-4AA0 Connection Type 1 Type 1 Type 2 Type 1 Type 1 type 12.5 12.5 84.5 84.5 Lengths n1 and n2 correspond to the distance between holes Output reactors Operating Instructions, 05/2017, A5E32846921B AE...
  • Page 15 Mechanical installation Table 3- 2 Dimensions of the output reactor, Part 2 (all data in mm) 6SL3000- 2AE41-0AA0 2AE41-4AA0 2AH34-7AA0 2AH35-8AA0 2AH38-1AA0 Connection Type 1 Type 1 Type 1 Type 1 Type 1 type 79.5 94.5 134.5 134.5 79.5 Lengths n1 and n2 correspond to the drill hole spacing Output reactors Operating Instructions, 05/2017, A5E32846921B AE...
  • Page 16 Mechanical installation Output reactors Operating Instructions, 05/2017, A5E32846921B AE...
  • Page 17: Electrical Installation

    Electrical installation Connection When connecting the output reactor, you must take into account the following conditions to ensure that it functions correctly: ● With analog control cables, connecting the shield at both ends can result in coupled-in noise. To prevent this, the shield must only be connected at one end on the Power Module.
  • Page 18 Electrical installation Tightening torques for screw connections The following tightening torques apply when tightening current-conducting connections (DC link connections, motor connections, busbars, cable lugs) and other connections (ground connections, protective ground connections, steel threaded connections/glands). Table 4- 1 Tightening torques for screw connections Thread Ground connections, protective Aluminum threaded connec-...
  • Page 19: Technical Specifications

    Technical specifications General technical data Table 5- 1 General technical data Product standard EN 61800-5-1 Specific technical data Table 5- 2 Technical data of output reactors, 380 V – 480 V 3 AC, part 1 Article No. 6SL3000- 2BE33-2AA0 2BE33-8AA0 2BE35-0AA0 2AE36-1AA0 Rated current...
  • Page 20 Technical specifications Table 5- 3 Technical data of output reactors, 380 V – 480 V 3 AC, part 2 Article No. 6SL3000- 2AE38-4AA0 2AE41-0AA0 2AE41-4AA0 Rated current 1405 Power loss - at 50 Hz 0.75 0.939 0.81 Connections - to the power module (1U1, 1V1, 2 x M12 1W1) 2 x M12...