Acquire Temperature Using Temperature Sensors - Siemens Sinamics G120P Operating Instructions Manual

Converter cabinet units 110 kw - 400 kw
Hide thumbs Also See for Sinamics G120P:
Table of Contents

Advertisement

Functions
7.7 Application-specific functions
7.7.12

Acquire temperature using temperature sensors

Analog input AI 2
Via the DIP switch and parameter p0756[2] , set the function of the analog input AI 2:
● p0756[2] = 2 or 3→ options for setting as current input
● p0756[2] = 6, 7 or 8 → options for setting as temperature sensor
Analog input AI 3
Analog input AI 3 is designed as a resistance input for a temperature sensor.
Setting options:
● p0756[3] = 6, 7 or 8 → options for setting as temperature sensor
Permissible temperature sensors
The temperature-dependent resistances Pt1000 or LG-Ni1000 are permissible as
temperature sensors. If you want to use the temperature signal as the actual value of the
temperature closed-loop controller, set p2264 = 755[2] or 755[3].
Connect the temperature sensor as follows:
● AI 2 (terminals 50, 51)
● AI 3 (terminals 52, 53)
Measuring ranges and alarm thresholds for LG-Ni1000
The measuring range of the LG-Ni1000 sensor extends from – 88° C ... 165° C. For values
outside this range, the inverter outputs alarm A03520 "Temperature sensor fault". The fault
type is displayed in r2124.
Measuring ranges and alarm thresholds for Pt1000
The measuring range of the Pt1000 sensor extends from –88° C ... 240° C. For values
outside this range, the inverter outputs alarm A03520 "Temperature sensor fault". The fault
type is displayed in r2124.
Fault values for temperature sensing via AI 2
● r2124 = 33: Wire break or sensor not connected
● r2124 = 34: Short-circuit
Fault values for temperature sensing via AI 3
● r2124 = 49: Wire break or sensor not connected
● r2124 = 50: Short-circuit