7.2.5

Three-wire control, method 1

With one control command, you enable the two other control commands. You switch the
motor off by withdrawing the enable (OFF1).
You switch the motor's direction of rotation to clockwise rotation with the positive edge of the
second control command. If the motor is still switched off, switch it on (ON).
You switch the motor's direction of rotation to counter-clockwise rotation with the positive
edge of the third control command. If the motor is still switched off, switch it on (ON).
Figure 7-5
Table 7- 5
Enable / OFF1
Parameter
p0015 = 19
Advanced setting
Interconnecting control commands with digital inputs of your choice (DI x).
p3330[0 ... n] = 722.x
p3331[0 ... n] = 722.x
p3332[0 ... n] = 722.x
Example
p3332[0 ... n] = 722.0
Inverter cabinet units
Operating Instructions, 12/2014, A5E32923362A
Three-wire control, method 1
Function table
ON clockwise
rotation
0
0 or 1
1
0→1
1
0
1
1
Description
Macro drive unit
Controlling the motor using
the digital inputs of the in-
verter:
BI: 2/3 wire control command 1 (enable/OFF1)
BI: 2/3 wire control command 2 (ON clockwise rotation)
BI: 2/3 wire control command 3 (ON counter-clockwise rotation)
DI 0: ON counter-clockwise rotation
ON counter-
Function
clockwise rotation
0 or 1
OFF1: The motor stops.
0
ON: Clockwise motor rotation.
0→1
ON: Counter-clockwise motor rota-
tion.
1
OFF1: The motor stops.
DI 0
Enable /
OFF1
Functions
7.2 Inverter control
DI 1
DI 2
ON clockwise
ON counter-
rotation
clockwise
rotation
341