Table 9- 4
YELLOW - variable
LED BF display for CANopen
In addition to the signal states "on" and "off" there are three different flashing frequencies:
Table 9- 5
GREEN - single flash Bus state "Stopped"
RED - single flash
RED - double flash
YELLOW - variable
9.2
System runtime
By evaluating the system runtime of the inverter, you can decide when you should replace
components subject to wear in time before they fail - such as fans, motors and gear units.
Principle of operation
The system runtime is started as soon as the Control Unit power supply is switched-on.
The system runtime stops when the Control Unit is switched off.
The system runtime comprises r2114[0] (milliseconds) and r2114[1] (days):
System runtime = r2114[1] × days + r2114[0] × milliseconds
Inverter cabinet units
Operating Instructions, 12/2014, A5E32923362A
Communication diagnostics via PROFIBUS DP
LED BF
Explanation
off
Cyclic data exchange (or PROFIBUS not used, p2030 = 0)
RED - slow
Bus fault - configuration fault
RED - fast
Bus fault
- no data exchange
- baud rate search
- no connection
Firmware update in progress
frequency
Communication diagnostics via CANopen
BF LED
Explanation
GREEN - on
Bus state "Operational"
GREEN - fast
Bus state "Pre-Operational"
RED - on
No bus
Alarm - limit reached
Error event in control (Error Control Event)
Firmware update in progress
frequency
Alarms, faults and system messages
9.2 System runtime
435