Electrical installation
4.8 Signal connections
Analog inputs
Table 4- 15
Analog inputs
Pin
Designation
3
AI0+
4
AI0-
10
AI1+
11
AI1-
50
AI2+/TEMP
51
GND
52
AI3+/TEMP
53
GND
Max. connectable cross-section: 1.5 mm²
AI: Analog input; GND: reference potential
1)
Analog outputs
Table 4- 16
Analog outputs
Pin
Designation
12
AO0+
13
GND
26
AO1+
27
GND
Max. connectable cross-section: 1.5 mm²
AO: Analog output; GND: reference potential
1)
82
1)
Differential input, switchable between current and voltage
Value range: 0 ... 10 V, -10 ... +10 V, 0/2 ... 10 V, 0/4 ... 20 mA
Differential input, switchable between current and voltage
Value range: 0 ... 10 V, -10 ... +10 V, 0/2 ... 10 V, 0/4 ... 20 mA
Non-isolated input, switchable between current and temperature sensors, type
Pt1000/LG-Ni1000
Value range:
- Current: 0/4 ... 20 mA
- Pt1000: +50 ... +250° C
- LG-Ni1000: +50 ... +150° C
Reference potential for the AI2/internal electronics ground
Non-isolated input for temperature sensors, type Pt1000/LG-Ni1000
Value range:
- Pt1000: +50 ... +250° C
- LG-Ni1000: +50 ... +150° C
Reference potential for the AI3/internal electronics ground
1)
Non-isolated output, freely programmable
Value range: 0 ... 10 V, 0/4 ... 20 mA
Reference potential for the AO0/internal electronics ground
Non-isolated output, freely programmable
Value range: 0 ... 10 V, 0/4 ... 20 mA
Reference potential for the AO1/internal electronics ground
Technical data
Technical data
Operating Instructions, 12/2014, A5E32923362A