Functions
7.7 Application-specific functions
Parameter
Description
p2394
Hibernation mode boost duration
0 (factory setting) ... 3599 s.
Before the inverter switches over into the hibernation mode, the motor is
accelerated for the time set in p2394 according to the acceleration ramp,
however, as a maximum to the speed set in p2395.
p2395
Energy-saving mode boost speed
0 (factory setting) to 21,000 rpm.
Before the inverter switches over into the hibernation mode, the motor is
accelerated for the time set in p2394 along the acceleration ramp, but not to
more than the speed set in p2395.
Caution:
The boost must not result in any overpressure or overflow.
p2396
Maximum hibernation mode shutdown time
0 (factory setting) to 863,999 s.
At the latest when this time expires, the inverter switches to normal opera-
tion and accelerates up to the start speed (p1080 + p2390). If the inverter is
switched to normal operation in advance, the shutdown time is reset to the
value set in this parameter.
With p2396 = 0, automatic switchover to normal operation after a certain
time is deactivated.
Status of the hibernation mode
Parameter
Description
r2273
Display of the setpoint/actual value deviation of the technology closed-loop controller
r2397
Actual hibernation mode output speed
Actual boost speed before the pulses are inhibited or the actual start speed after restart.
r2399
Hibernation mode status word
00 Hibernation mode enabled (p2398 <> 0)
01 Hibernation mode active
02 Hibernation mode delay time active
03 Hibernation mode boost active
04 Hibernation mode motor switched off
05 Hibernation mode motor switched off, cyclic restart active
06 Energy-saving mode motor restarts
07 Hibernation mode supplies the total setpoint of the ramp-function generator
08 Hibernation mode bypasses the ramp-function generator in the setpoint channel