Siemens Sinamics G120P Operating Instructions Manual page 235

Converter cabinet units 110 kw - 400 kw
Hide thumbs Also See for Sinamics G120P:
Table of Contents

Advertisement

Table 6- 21
Assigning the Modbus register to the parameters of the Control Unit
Modbus
Description
Reg.
No.
Process data
Control data
40100
Control word
40101
Main setpoint
Status data
40110
Status word
40111
Main actual value
Parameter data
Digital outputs
40200
DO 0
40201
DO 1
40202
DO 2
Analog outputs
40220
AO 0
40221
AO 1
Digital inputs
40240
DI 0
40241
DI 1
40242
DI 2
40243
DI 3
40244
DI 4
40245
DI 5
Analog inputs
40260
AI 0
40261
AI 1
40262
AI 2
40263
AI 3
Inverter identification
40300
Powerstack number
40301
Inverter firmware
Inverter data
40320
Rated power of the power unit
40321
Current limit
40322
Ramp-up time
40323
Ramp-down time
40324
Reference speed
Inverter diagnostics
40340
Speed setpoint
40341
Actual speed value
Inverter cabinet units
Operating Instructions, 12/2014, A5E32923362A
Modbus
Unit
Scaling
access
factor
R/W
--
1
R/W
--
1
R
--
1
R
--
1
R/W
--
1
R/W
--
1
R/W
--
1
R
%
100
R
%
100
R
--
1
R
--
1
R
--
1
R
--
1
R
--
1
R
--
1
R
%
100
R
%
100
R
%
100
R
%
100
R
--
1
R
--
0.0001
R
kW
100
R/W
%
10
R/W
s
100
R/W
s
100
R/W
RPM
1
R
RPM
1
R
RPM
1
6.8 Communication via RS485
On/Off text
Data / parameter
or value range
Process data 1
Process data 2
Process data 1
Process data 2
HIGH
LOW
p0730, r747.0, p748.0
HIGH
LOW
p0731, r747.1, p748.1
HIGH
LOW
p0732, r747.2, p748.2
-100.0 ... 100.0
r0774.0
-100.0 ... 100.0
r0774.1
HIGH
LOW
r0722.0
HIGH
LOW
r0722.1
HIGH
LOW
r0722.2
HIGH
LOW
r0722.3
HIGH
LOW
r0722.4
HIGH
LOW
r0722.5
-300.0 ... 300.0
r0755 [0]
-300.0 ... 300.0
r0755 [1]
-300.0 ... 300.0
r0755 [2]
-300.0 ... 300.0
r0755 [3]
0 ... 32767
r0200
0.00 ... 327.67
r0018
0 ... 327.67
r0206
10.0 ... 400.0
p0640
0.00 ... 650.0
p1120
0.00 ... 650.0
p1121
6.000 ... 32767
p2000
-16250 ... 16250
r0020
-16250 ... 16250
r0022
Operation
235