Technical Specifications; Section Content; General Data - Siemens Sinamics G120P Operating Instructions Manual

Converter cabinet units 110 kw - 400 kw
Hide thumbs Also See for Sinamics G120P:
Table of Contents

Advertisement

Technical specifications

11.1

Section content

This chapter provides information on the following:
● General and specific technical specifications for the devices.
● Information on restrictions that apply when the devices are used in unfavorable ambient
conditions (derating)
11.2

General data

Table 11- 1
General technical data
Electrical data
Line system configurations
Line frequency
Output frequency
Displacement factor cosφ
Power factor λ
Converter efficiency
Overvoltage category
Mechanical data
Degree of protection
Class of protection
Touch protection
Cabinet system
Paint finish
Sound pressure level L
pA
(1 m)
Cooling method
Compliance with standards
Standards
CE mark
RI suppression
Inverter cabinet units
Operating Instructions, 12/2014, A5E32923362A
Grounded TN/TT systems and non-grounded IT systems
47 ... 63 Hz
0 ... 100 Hz
0.96
0.75 ... 0.93
> 98 %
III according to EN 61800-5-1
IP20 (higher degrees of protection up to IP54 optional)
I according to EN 61800-5-1
EN 50274 and BGV A3 when used as intended
Schäfer industrial housing IS-1, doors with double-barb lock, base plates with cable entry
possibilities.
RAL 7035 (indoor requirements)
for 50 Hz line frequency: ≤ 69 dB(A)
for 60 Hz line frequency: ≤ 69 dB(A)
Forced air cooling AF according to EN 60146
EN 60146-1, EN 61800-2, EN 61800-3, EN 61800-5-1, EN 60204-1, EN 60529
In accordance with EMC Directive No. 2004/108/EC and Low-Voltage Directive No.
2006/95/EC and Machinery Directive No. 2006/42/EC
In accordance with the EMC product standard for variable-speed drives EN 61800-3, "sec-
ond environment."
Application in "first environment" possible with line filters (option L00)
11
2)
.
1)
469