Electrical installation
4.8 Signal connections
Terminal
Name
10
NC
11
HS1
12
HS2
Maximum connection cross section: 2.5 mm²
Minimum connection cross section: 0.2 mm²
Maximum tightening torque: 0.5 Nm (4.5 ... 5 lb.in)
102
Significance
Not connected
Line contactor control
Line contactor control
Input/
Technical data
output
Output
Contact type: NO contact
Maximum load current: 4 A, 230 V AC, cosφ
Output
= 0.6
Floating
A device to protect against overload and
short-circuit is required to supply the unpro-
tected output.
Surge suppressors must be connected to
the excitation coil of the main contactor (e.g.
RC element).
To control the main contactor, the following
contact characteristic values of the relay
according to UL apply:
250 V AC, 10 A (NC and NO), general
purpose, 85 °C,
24 V DC, 10 A (NC and NO), general
purpose, 85 °C,
30 V DC, 8 A (NO), 6 A (NC), general
purpose, 85 °C
B300 (NC and NO), pilot duty, 85 °C
R300 (NC and NO), pilot duty, 85 °C
24 V AC, 2.0 A (NC and NO), pilot duty,
85 °C