Table 6- 13
Error value in the parameter response
Error
Significance
value 1
00 hex
Illegal parameter number (access to a parameter that does not exist)
01 hex
Parameter value cannot be changed (change request for a parameter value that cannot be changed)
02 hex
Lower or upper value limit exceeded (change request with a value outside the value limits)
03 hex
Incorrect subindex (access to a parameter index that does not exist)
04 hex
No array (access with a subindex to non-indexed parameters)
05 hex
Incorrect data type (change request with a value that does not match the data type of the parameter)
06 hex
Setting not permitted, only resetting (change request with a value not equal to 0 without permission)
07 hex
Descriptive element cannot be changed (change request to a descriptive element that cannot be changed)
09 hex
Description data not available (access to a description that does not exist, parameter value is available)
0B hex
No master control (change request but with no master control)
0F hex
Text array does not exist (although the parameter value is available, the request is made to a text array that
does not exist)
11 hex
Request cannot be executed due to the operating state (access is not possible for temporary reasons that are
not specified)
14 hex
Inadmissible value (change request with a value that is within the limits but which is illegal for other permanent
reasons, i.e. a parameter with defined individual values)
15 hex
Response too long (the length of the actual response exceeds the maximum transfer length)
16 hex
Illegal parameter address
subindex or a combination of these)
17 hex
Illegal format (change request for an illegal or unsupported format)
18 hex
Number of values not consistent
in the parameter address)
19 hex
Drive object does not exist (access to a drive object that does not exist)
6B hex
No change access for a closed-loop controller that is enabled
6C hex
Unknown unit.
6E hex
Change request is only possible when the motor is being commissioned (p0010 = 3).
6F hex
Change request is only possible when the power unit is being commissioned (p0010 = 2).
70 hex
Change request is only possible for quick commissioning (basic commissioning) (p0010 = 1).
71 hex
Change request is only possible if the inverter is ready (p0010 = 0).
72 hex
Change request is only possible for a parameter reset (restore to factory setting) (p0010 = 30).
73 hex
Change request is only possible during commissioning of the safety functions (p0010 = 95).
74 hex
Change request is only possible when a technological application/unit is being commissioned (p0010 = 5).
75 hex
Change request is only possible in a commissioning state (p0010 ≠ 0).
76 hex
Change request is not possible for internal reasons (p0010 = 29).
77 hex
Change request is not possible at download.
81 hex
Change request is not possible at download.
82 hex
Transfer of the control authority (master) is inhibited by BI: p0806.
83 hex
Desired interconnection is not possible (the connector output does not supply a float value although the con-
nector input requires a float value)
84 hex
Inverter does not accept a change request (inverter is busy with internal calculations, see parameter r3996 in
the inverter List Manual)
85 hex
No access methods defined.
Inverter cabinet units
Operating Instructions, 12/2014, A5E32923362A
(illegal or unsupported value for attribute, number of elements, parameter number,
(number of values of the parameter data to not match the number of elements
6.5 PROFIdrive profile for PROFIBUS and PROFINET