List Of Alarms And Faults - Siemens Sinamics G120P Operating Instructions Manual

Converter cabinet units 110 kw - 400 kw
Hide thumbs Also See for Sinamics G120P:
Table of Contents

Advertisement

9.5

List of alarms and faults

Axxxxx Alarm
Fyyyyy: Fault
Table 9- 6
Faults that can be acknowledged only by switching the inverter off and on again (POWER ON)
Number
Cause
F01000
Software fault in CU
F01001
Floating-point exception
F01015
Software fault in CU
F01018
Power-up aborted more than once
F01040
Parameters must be saved
F01044
Loading of memory data card de-
fective
F01105
CU: Insufficient memory
F01205
CU: Time slice overflow
F01250
CU hardware fault
F1257
Firmware obsolete
F01512
An attempt has been made to
establish a conversion factor for
scaling which is not present
F01662
CU hardware fault
F30022
Power Module: Monitoring V
F30052
Incorrect Power Module data
F30662
CU hardware fault
F30664
CU power up aborted
F30850
Software fault in Power Module
F30950
Software fault in Power Module
Inverter cabinet units
Operating Instructions, 12/2014, A5E32923362A
Remedy
Replace CU.
Switch CU off and on again.
Upgrade firmware or contact technical support.
After this fault is output, the inverter powers up with the factory settings.
Remedy: Back up factory setting with p0971=1. Switch CU off and on
again. Recommission the inverter.
Save parameters (p0971).
Switch CU off and on again.
Replace memory card or CU.
Reduce number of data records.
Contact technical support.
Replace CU.
Upgrade the firmware in the CU.
Create scaling or check transfer value.
Switch CU off and on again, upgrade firmware, or contact technical sup-
port.
Check or replace Power Module.
CE
Replace Power Module or upgrade CU firmware.
Switch CU off and on again, upgrade firmware, or contact technical sup-
port.
Switch CU off and on again, upgrade firmware, or contact technical sup-
port.
Replace Power Module or contact technical support.
Replace Power Module or contact technical support.
Alarms, faults and system messages
9.5 List of alarms and faults
445

Advertisement

Table of Contents
loading

Table of Contents