Functions
7.2 Inverter control
7.2.4

Two-wire control, method 3

You switch the motor on and off using a control command (ON/OFF1) and at the same time
select clockwise motor rotation. You also use the other control command to switch the motor
on and off, but in this case you select counter-clockwise rotation for the motor.
Unlike method 2, the inverter will accept the control commands at any time, regardless of the
motor speed.
Figure 7-4
Table 7- 4
ON/OFF1 clockwise
Parameter
p0015 = 18
Advanced setting
Interconnecting control commands with digital inputs of your choice (DI x).
p3330[0 ... n] = 722.x
p3331[0 ... n] = 722.x
Example
p3331[0 ... n] = 722.2
340
Two-wire control, method 3
Function table
ON/OFF1 counter-
rotation
clockwise rotation
0
1
0
1
Description
Macro drive unit
Controlling the motor using the digital
inputs of the inverter:
BI: 2/3 wire control command 1 (ON/OFF1 clockwise rotation)
BI: 2/3 wire control command 2 (ON/OFF1 counter-clockwise rotation)
DI 2: ON/OFF1 counter-clockwise rotation
Function
0
OFF1: The motor stops.
0
ON: Clockwise motor rotation.
1
ON: Counter-clockwise motor rotation.
1
OFF1: The motor stops.
DI 0
ON/OFF1 clock-
wise rotation
Operating Instructions, 12/2014, A5E32923362A
DI 1
ON/OFF1 coun-
ter-clockwise
rotation