Siemens Sinamics G120P Operating Instructions Manual page 478

Converter cabinet units 110 kw - 400 kw
Hide thumbs Also See for Sinamics G120P:
Table of Contents

Advertisement

Technical specifications
11.3 Technical specifications
Article number
Motor cable length, max.
- compliant with categories C2 and C3
according to EN 61800-3, shielded
- non-compliant with the limit values for
interference and without output choke
or dv/dt filter, unshielded
- non-compliant with the limit values for
interference and with output choke or
dv/dt filter, shielded/unshielded
Dimensions (standard version)
- Width
- Height
8)
- Depth
Power Module frame size
Weight (without options), approx.
Recommended protection
- Line protection
(with option L26)
Rated current
frame size to IEC 60269
- Line and semiconductor protection
(without option L26)
Rated current
Frame size to IEC 60269
Short-circuit current rating according to
IEC
9)
Minimum short-circuit current
- For 3NE1 fuses
- For 3NA3 fuses
Rated output of a typical 4-pole standard induction motor based on I
1)
Rated output of a typical 4-pole standard induction motor based on I
2)
The base-load current I
3)
"Overload capability").
The base-load current I
4)
capability").
The current values given here are based on the rated output current.
5)
The recommendations for the North American market in AWG or MCM must be taken from the appropriate NEC (National
6)
Electrical Code) or CEC (Canadian Electrical Code) standards.
The connecting blocks can be damaged when using longer screws.
7)
The cabinet height increases by 300 mm for IP20 and IP21 degrees of protection, and by 400 mm for IP23, IP43 and IP54
8)
degrees of protection.
In conjunction with the specified fuses or circuit breakers.
9)
Minimum current required for reliable activation of the designated protection devices.
10)
Caution: If the minimum short circuit current is not reached, the rupture time of the fuses is increased, which can lead to
damage.
478
6SL3710- 1PE32-1AA0
m
m
m
mm
mm
mm
kg
A
A
kA
10)
A
A
is based on a duty cycle of 110% for 60 s or 135% for 3 s with a duty cycle duration of 300 s (see
L
is based on a duty cycle of 150% for 60 s with a duty cycle duration of 300 s (see "Overload
H
1PE32-5AA0
100
100
200
200
300/450
300/450
1000
1000
2000
2000
600
600
GX
GX
360
360
3NA3144
3NA3252
250
315
1
2
3NE1230-2
3NE1331-2
315
350
1
2
65
65
3000
3600
5800
7300
or I
at 3-phase 400 V AC 50 Hz.
L
H
or I
at 3-phase 460 V AC 60 Hz.
L
H
1PE33-0AA0
100
200
300/450
1000
2000
600
GX
370
3NA3260
400
2
3NE1333-2
450
2
65
4400
9500
Inverter cabinet units
Operating Instructions, 12/2014, A5E32923362A