Operation
6.4 Communication via PROFIBUS
Procedure
Proceed as follows to configure communication to the controller using GSD:
1. Obtain the GSD file of the inverter.
You have two options:
– You can find the GSD of the SINAMICS inverter on the Internet
– The GSD is saved in the inverter. If you insert the memory card in the inverter and set
2. Import the GSD into the configuring tool of your controller.
3. Configure the communication between the controller and the inverter in your control.
6.4.4
Setting the address
You set the PROFIBUS address of the inverter using
the address switch on the Control Unit, in parameter
p0918 or in STARTER.
In parameter p0918 (factory setting: 126) or in
STARTER, you can only set the address if all ad-
dress switches are set to "OFF" (0) or "ON" (1).
If you have specified a valid address with the address
switches, this address will always be the one that
takes effect and parameter p0918 cannot be
changed.
Valid address area: 1 ... 125
The positions of the address switches are described
in Section: CU230P-2 DP Control Unit (option K97)
(Page 78).