Mechanical installation
3.3 Assembly
3.3.2.2
Requirements on the levelness of the floor
The foundation at the installation location must be horizontal and level, to ensure proper
functioning of the cabinet units.
● Care must be taken to ensure that the doors can be opened and closed and that the
locking systems work properly.
● Flat sections (such as doors, side panels and hoods) must be sealed correctly to ensure
compliance with the specified degree of protection.
● When cabinets are connected (e.g., transport units), air inlets caused by gaps must be
prevented.
Figure 3-1
The following points must be observed to ensure full functionality of the cabinet units:
● The foundation must be level and horizontal.
● Irregularities must be leveled out.
● Gaps where air can enter caused by leveling measures (e.g.:
sealed.
38
Requirements on the levelness of the floor
①
in the diagram) must be
Inverter cabinet units
Operating Instructions, 12/2014, A5E32923362A