Bypass - Siemens Sinamics G120P Operating Instructions Manual

Converter cabinet units 110 kw - 400 kw
Hide thumbs Also See for Sinamics G120P:
Table of Contents

Advertisement

Functions
7.7 Application-specific functions
7.7.16

Bypass

The bypass function switches the motor from inverter operation to line system operation. The
following options are possible:
● Bypass function when activating via a control signal (p1267.0 = 1)
● Bypass function depending on the speed (p1267.1 = 1)
The inverter controls two contactors via its digital outputs. The inverter analyses the
feedback signals from the contactors via its digital inputs. If using direct connection logic
(high level = ON), both contactors should be NO contacts.
Figure 7-28
Note
Flying restart must be activated for the bypass function (p1200 = 1 or 4).
Note
Bypass mode in the essential service mode
The special features for bypass mode in the essential service mode are described in Section
Essential service mode (Page 401).
412
Bypass circuit for control using the inverter
Inverter cabinet units
Operating Instructions, 12/2014, A5E32923362A