6.5.1.2

Control and status word 3

The control and status words fulfill the specifications of PROFIdrive profile version 4.1 for the
"closed-loop speed controlled" mode.
Control word 3 (STW3)
Control word 3 has the following default assignment. You can change the signal
interconnection. See also function diagram 2446.
Bit Value Significance
Telegram 350
0
1
Fixed setpoint, bit 0
1
1
Fixed setpoint, bit 1
2
1
Fixed setpoint, bit 2
3
1
Fixed setpoint, bit 3
4
1
DDS selection, bit 0
5
1
DDS selection, bit 1
6
Reserved
7
Reserved
8
1
Technology controller enable
9
1
DC braking enable
10 –
Reserved
11 1
1 = Enable droop
12 1
Torque control active
0
Closed-loop speed control active
13 1
No external fault
0
External fault is active (F07860)
14 –
Reserved
15 1
CDS bit 1
If you switch from telegram 350 to a different one, then the inverter sets all interconnections p1020, ... to "0". Exception:
1)
p2106 = 1.
Inverter cabinet units
Operating Instructions, 12/2014, A5E32923362A
6.5 PROFIdrive profile for PROFIBUS and PROFINET
Explanation
Selects up to 16 different fixed setpoints.
Changes over between settings for differ-
ent motors (drive data sets).
--
--
Enable or inhibit speed controller droop.
Changes over the control mode for vector
control.
--
Changes over between settings for differ-
ent operation interfaces (command data
sets).
Operation
Signal interconnection
in the inverter
1)
p1020[0] = r2093.0
p1021[0] = r2093.1
p1022[0] = r2093.2
p1023[0] = r2093.3
p0820 = r2093.4
p0821 = r2093.5
p2200[0] = r2093.8
p1230[0] = r2093.9
p1492[0] = r2093.11
p1501[0] = r2093.12
p2106[0] = r2093.13
p0811[0] = r2093.15
191