Functions
7.7 Application-specific functions
Set the parameters of the automatic restart function.
The method of operation of the parameters is explained in the following diagram and in the
table.
The inverter automatically acknowledges faults under the following conditions:
1
•
•
•
The inverter attempts to automatically switch the motor on under the following conditions:
2
•
•
If no fault has occurred one second after flying restart and magnetizing (r0056.4 = 1), the start at-
3
tempt was successful.
Figure 7-21
388
p1210 = 1 or 26: Always.
p1210 = 4 or 6: If the command to switch the motor on is available at a digital input or via the
fieldbus (ON/OFF1 = 1).
p1210 = 14 or 16: Never.
p1210 = 1: Never.
p1210 = 4, 6, 14, 16, or 26: If the command to switch the motor on is available at a digital input
or via the fieldbus (ON/OFF1 = 1).
Time response of the automatic restart
Inverter cabinet units
Operating Instructions, 12/2014, A5E32923362A