Operation
6.5 PROFIdrive profile for PROFIBUS and PROFINET
Status word 1 (ZSW1)
Status word 1 (bits 0 ... 10 in accordance with PROFIdrive profile and VIK/NAMUR, bits 11
... 15 specific to the inverter). See also function diagram 2451/2452.
Bit
Significance
Telegram 20
All other tele-
grams
0
1 = Ready to start
1
1 = Ready
2
1 = Operation enabled
3
1 = Fault active
4
1 = OFF2 inactive
5
1 = OFF3 inactive
6
1 = Closing lockout active
7
1 = Alarm active
8
1 = Speed deviation within the
tolerance range
9
1 = Master control requested
10
1 = Comparison speed reached or
exceeded
11
0 = I, M or P limit reached
12
---
1 = Holding
1)
brake open
13
0 = Alarm, motor overtemperature --
14
1 = Motor rotates clockwise
0 = Motor rotates counterclock-
wise
15
1 = CDS dis-
0 = Alarm, in-
play
verter thermal
overload
If you change over from another telegram to telegram 20, then the assignment of the previous telegram is kept.
1)
190
Comments
The power supply is switched on; electronics initialized;
pulses locked.
The motor is switched on (ON/OFF1 = 1), no fault is active.
With the command "Enable operation" (STW1.3), the invert-
er switches on the motor.
The motor follows the setpoint. See control word 1, bit 3.
The inverter has a fault. Acknowledge fault using STW1.7.
Coast down to standstill is not active.
Quick stop is not active.
It is only possible to switch on the motor after an OFF1
followed by ON.
The motor remains switched on; no acknowledgement is
necessary.
Setpoint / actual value deviation within the tolerance range.
The automation system is requested to accept the inverter
control.
Speed is greater than or equal to the corresponding maxi-
mum speed.
Comparison value for current, torque or power has been
reached or exceeded.
Signal to open and close a motor holding brake.
Internal inverter actual value > 0
Internal inverter actual value < 0
Signal intercon-
nection in the
inverter
p2080[0] =
r0899.0
p2080[1] =
r0899.1
p2080[2] =
r0899.2
p2080[3] =
r2139.3
p2080[4] =
r0899.4
p2080[5] =
r0899.5
p2080[6] =
r0899.6
p2080[7] =
r2139.7
p2080[8] =
r2197.7
p2080[9] =
r0899.9
p2080[10] =
r2199.1
p2080[11] =
r1407.7
p2080[12] =
r0899.12
p2080[13] =
r2135.14
p2080[14] =
r2197.3
p2080[15] =
r0836.0 /
r2135.15
Inverter cabinet units
Operating Instructions, 12/2014, A5E32923362A