Section 1: Installation; Unpacking, Storage And Handling; Recommended Mounting Position; Wiring - Siemens 7SR224 Manual

Recloser controller
Hide thumbs Also See for 7SR224:
Table of Contents

Advertisement

Section 1: Installation

1.1

Unpacking, Storage and Handling

On receipt remove the relay from the container in which it was received and inspect it for obvious damage. It is
recommended that the relay not be removed from its case.
If damage has been sustained a claim should immediately be made against the carrier, also inform Siemens
Protection Devices Limited, and the local Siemens agent, using the Defect Report Form in the Maintenance
section of this manual.
When not required for immediate use, the relay should be returned to its original carton and stored in a clean, dry
place.
The relay contains static sensitive devices, which are susceptible to damage due to static discharge. The relay's
electronic circuits are protected from damage by static discharge when the relay is housed in its case.
There can be no requirement to disassemble any relay, since there are no user serviceable parts in the relay. If
any modules have been tampered with, then the guarantee will be invalidated. Siemens Protection Devices
Limited reserves the right to charge for any subsequent repairs.

1.2 Recommended Mounting Position

The relay uses a liquid crystal display (LCD) which is used in the programming and for operation. The LCD has a
vertical viewing angle of ± 30˚ and is back–lit. However, the best viewing position is at eye level, and this is
particularly important given its control features.
The relay should be mounted on the circuit breaker (or protection panel) to allow the operator the best access to
the relay functions

1.3 Wiring

The product should be wired according to the scheme requirements, with reference to the appropriate wiring
diagram. Refer to the appropriate Diagrams and Parameters document for a cross reference of wiring diagrams
and models.
1.4

Earthing

Terminal 28 of the PSU (Power Supply Unit) should be solidly earthed by a direct connection to the panel earth.
The Relay case earth stud connection should be connected to terminal 28 of the PSU.
It is normal practice to additionally 'daisy chain' together the case (safety) earths of all the Relays installed in a
panel to prevent earth current loops posing a risk to personnel.

1.5 Ancillary Equipment

The relay can be interrogated locally or remotely. For local interrogation a portable PC with suitable version of
MS Windows (2000 SP4 or XP SP2) and Reydisp Evolution™ software is required. The PC is connected to the
front USB port of the relay.
1.6
Equipment Operating Conditions Current Transformer
Circuits
!
The secondary circuit of a live CT must not be open circuited. Non-observance of this precaution can result in
injury to personnel or damage to equipment
©2010 Siemens Protection Devices Limited
7SR224 Argus Installation
Chapter 5 Page 3 of 16

Advertisement

Table of Contents
loading

Table of Contents