Flush-Mounting Devices; Basic Rules For Expansion - Siemens SIPROTEC 5 V7.80 Operation

Table of Contents

Advertisement

Expanding Devices

2.1 Flush-Mounting Devices

2.1
Flush-Mounting Devices

Basic Rules for Expansion

2.1.1
NOTE
i
i
Prepare the following tools for the device expansion:
Phillips screwdriver size PZ1 and PZ2
Screwdriver DIN 4 x 0.8
During assembly, use the prescribed torques
Comply with the following basic rules when expanding devices:
Always fit the base module on the left in the 1st device row.
²
Always fit the expansion modules from left to right.
²
Always fit the expansion module with the key switches as the 1st module next to the base module.
²
Always fit the expansion modules without LEDs last.
²
Always install a power-supply module PS203 on the left as the first unit in the 2nd device row.
²
Note that the PS203 must always have the same rated voltage as the base module.
²
In the 2nd device row, mount only input and output modules without LEDs.
²
[dweinzei-030211-01.tif, 2, --_--]
Figure 2-1
22
Device Row of a Flush-Mounting Device
SIPROTEC 5, Operation, Manual
C53000-G5040-C003-9, Edition 06.2018

Advertisement

Table of Contents
loading

Table of Contents