Technical Design; Led Indication - Siemens SSE161.05U Manual

Electromotoric actuator
Table of Contents

Advertisement

Use
For 2-way & 3-way 599 Series Zone Valves: 599-00210 - 599-00214, 599-00230 - 599-
00234, 599-00510 - 599-00514, 599-00530 - 599-00534
Typically in chilled ceiling, VAV and fan coil unit applications
Max.10 units of SSE161.05U, SSF161.05U can operate in parallel, provided the
controller output suffices.

Technical design

When the actuator is driven by DC 0...10 V positioning signal, it produces a stroke, which is
transmitted to the valve stem.
DC 0...10 V control signal
The valve opens / closes in proportion to the
control signal at Y.
At DC 0 V, the SSE161.05U actuator stem is
extended, and the normally open valve is fully
closed.
At DC 0 V, the SSF161.05U actuator stem is
retracted and the normally open valve is fully open.
When no power is supplied, the actuator maintains
its current position.
Y = Control signal Y [V]
H = Percentage of calibrated valve stroke

LED indication

2
Siemens
Smart Infrastructure
Status
Variants
 Modulation: Stem retracting
Modulation: Stem extending
Stem position
Calibration
Error
Manual operation
LED indication patterns
SSE161.05U, SSF161.05U
Flashing green in sequence: LED1-->LED2-->LED3 (500 ms each)
Flashing green in sequence: LED3-->LED2-->LED1 (500 ms each)
At H0 (fully extended for SSE and fully retracted for SSF) - H40:
Constant green (LED3)
At H40 - H60: Constant green (LED2)
At H60 - H100 (fully retracted for SSE and fully extended for SSF):
Constant green (LED1)
Flashing green (LED2): 100 ms on, 100 ms off
Constant red (LED2)
Flashing green/red alternatively (LED2): Green 500 ms, red 500 ms
A6V12681514_enUS_b
06/15/2023

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ssf161.05u