8.4.3 Activating the PROFIBUS DP Communication Module (Field Bus Interface) and Setting the
Station Address via the Device Interface using the "Soft Starter ES Premium" or the "Soft
Starter ES + SP1" Software
SIRIUS 3RW44 manual
GWA 4NEB 535 2195-02 DS 06
Carry out the following steps to activate the communication module:
1. Use an interface cable to connect the 3RW44 soft starter to a PC on which the
"Soft Starter ES Premium" or the "Soft Starter ES + Service Pack 1" software is
installed.
2. Start the "Soft Starter ES Premium" or "Soft Starter ES + Service Pack 1"
software.
3. Select "Switching device > Open online" in the menu.
4. In the "Open online" dialog box, select the "Local device interface" option and the
desired COM port under "Interface".
5. Click "OK".
6. Select "Device configuration" on the left-hand side of the window.
7. Activate the "Field bus interface" control box on the right-hand side of the
window.
8. Select "Device parameters > Field bus" on the left-hand side of the window.
PROFIBUS DP Communication Module
8-13