Configure advanced options for process measurement
6.7.2
Interaction between Process Variable Fault Action and
other fault actions
The setting of Process Variable Fault Action affects the operation of the mA outputs,
frequency outputs, and discrete outputs if the corresponding output fault actions are set
to None.
Interaction between Process Variable Fault Action and mA Output Fault Action
If mA Output Fault Action is set to None, the mA output signal depends on the setting of
Process Variable Fault Action.
If the device detects a fault condition:
1.
2.
If you want the mA output to continue to report process data during fault conditions, you
must set both mA Output Fault Action and Process Variable Fault Action to None.
Interaction between Process Variable Fault Action and Frequency Output Fault Action
If Frequency Output Fault Action is set to None, the frequency output signal depends on the
setting of Process Variable Fault Action.
If the device detects a fault condition:
1.
2.
If you want the frequency output to continue to report process data during fault
conditions, you must set both Frequency Output Fault Action and Process Variable Fault
Action to None.
Interaction between Process Variable Fault Action and Discrete Output Fault Action
If Discrete Output Fault Action is set to None and Discrete Output Source is set to Flow Rate
Switch, the discrete output state during a fault depends on the setting of Process Variable
Fault Action.
If the device detects a fault condition:
1.
2.
96
Process Variable Fault Action is evaluated and applied.
mA Output Fault Action is evaluated.
If it is set to None, the output reports the value associated with the setting of
Process Variable Fault Action.
If it is set to any other option, the output performs the specified fault action.
Process Variable Fault Action is evaluated and applied.
Frequency Output Fault Action is evaluated.
If it is set to None, the output reports the value associated with the setting of
Process Variable Fault Action.
If it is set to any other option, the output performs the specified fault action.
Process Variable Fault Action is evaluated and applied.
Discrete Output Fault Action is evaluated.
Micro Motion Model 5700 with Ethernet Transmitters