Integrate the meter with the control system
Label
None (default)
Fault indication with the discrete output
To indicate faults via the discrete output, set Discrete Output Source to Fault. Then, if a
fault occurs, the discrete output is always ON and the setting of Discrete Output Fault
Action is ignored.
8.7

Configure the discrete input

The discrete input is used to initiate a transmitter action from a remote input device.
8.7.1

Configure Discrete Input Action

Display
ProLink III
Web browser
Overview
Discrete Input Action controls the action or actions that the transmitter will perform when
the discrete input transitions from OFF to ON.
CAUTION!
Before assigning actions to a discrete input, check the status of the remote input device. If it is
ON, all assigned actions will be performed when the new configuration is implemented. If this
is not acceptable, change the status of the remote input device or wait until an appropriate
time to assign actions.
Procedure
Set Discrete Input Action as desired.
Default: None
138
Polarity=Active High
Discrete output is controlled by its assignment
Configure Discrete Input Action
Configure Discrete Input Polarity
Menu > Configuration > Inputs/Outputs > Channel C > I/O Settings > Assign Actions
Device Tools > Configuration > I/O > Inputs > Action Assignment
Configuration > Inputs/Outputs > Channel C > Discrete Input > Action Assignment
Discrete output behavior
Polarity=Active Low
(Section 8.7.1)
(Section 8.7.2)