8.5.4
Configure Frequency Output Fault Action
Display
ProLink III
Web browser
Overview
Frequency Output Fault Action controls the behavior of the frequency output if the
transmitter detects a fault condition.
Important
•
•
Procedure
1.
2.
Related information
Options for Frequency Output Fault Action
Label
Upscale
Downscale
Configuration and Use Manual
Menu > Configuration > Inputs/Outputs > Channel C > I/O Settings > Fault Action
Device Tools > Configuration > I/O > Outputs > Frequency Output x > Fault Action
Configuration > Inputs/Outputs > Channel C > Frequency Output > Fault Action
The fault action is implemented only if Alert Severity is set to Failure. If Alert Severity is set to
any other option, the fault action is not implemented.
For some faults only: If Fault Timeout is set to a non-zero value, the transmitter will not
implement the fault action until the timeout has elapsed.
Set Frequency Output Fault Action as desired.
•
Default: Downscale
Important
If you set Frequency Output Fault Action to None, the frequency output will be controlled by
the setting of Process Variable Fault Action. In most cases, if you set Frequency Output Fault
Action to None, you should also set Process Variable Fault Action to None.
If you set Frequency Output Fault Action to Upscale, set Frequency Fault Level to the
desired value.
•
Default: 14500 Hz
•
Range: 10 Hz to 14500 Hz
Configure Process Variable Fault Action
Integrate the meter with the control system
Frequency output behavior
Goes to configured Upscale value:
•
Default: 14500 Hz
•
Range: 10 Hz to 14500 Hz
0 Hz
133