Configure Ma Output Source - Emerson Micro Motion 5700 Configuration And Use Manual

Model 5700 with ethernet
Hide thumbs Also See for Micro Motion 5700:
Table of Contents

Advertisement

8.4.1

Configure mA Output Source

Display
ProLink III
Web browser
Overview
mA Output Source specifies the process variable that is reported by the mA output.
Prerequisites
Procedure
Set mA Output Process Variable as desired.
Defaults:
mA Output 1: Mass Flow Rate
Postrequisites
If you change the configuration of mA Output Source, verify the settings of Lower Range
Value and Upper Range Value. The transmitter automatically loads a set of values, and
these values may not be appropriate for your application.
Related information
Options for mA Output Source
The transmitter provides a basic set of options for mA Output Source, plus several
application-specific options. Different communications tools may use different labels for
the options.
Process variable
Standard
Mass flow rate
Volume flow rate
Configuration and Use Manual
Menu > Configuration > Inputs/Outputs > Channel C > I/O Settings > Source
Device Tools > Configuration > I/O > Channels > Channel C > mA Output
Configuration > Inputs/Outputs > Channel C > Channel Type > mA Output
If you plan to configure the output to report volume flow, ensure that you have set
Volume Flow Type as desired: Liquid or Gas Standard Volume.
If you plan to configure an output to report a concentration measurement process
variable, ensure that the concentration measurement application is configured so
that the desired variable is available.
Configure Lower Range Value (LRV) and Upper Range Value (URV) for the mA output
Display
Mass Flow Rate
Volume Flow Rate
Integrate the meter with the control system
Label
ProLink III
Mass Flow Rate
Volume Flow Rate
Web browser
Mass Flow Rate
Volume Flow Rate
119