Measurement support
If you plan to use a fixed value during the SMV test, ensure that all affected control loops
are prepared for the interruption in process measurement. The test will run for
approximately 140 seconds.
Run an SMV test using the display
1.
2.
3.
4.
Postrequisites
View the results and take any appropriate actions.
162
Maintain a constant flow rate. If possible, stop flow through the sensor.
Avoid changes to fluid composition, for example, two-phase flow or settling.
Run an SMV test using the display
Run an SMV test using ProLink III
Run an SMV test using a web browser
Read the Prerequisites in
Choose Menu > Service Tools > Verification and Calibration > Smart Meter
Verification > Run SMV.
Select the desired output behavior.
Option
Description
Continue Measuring During the test, all outputs will continue to report their assigned proc-
ess variables. The test will run for approximately 90 seconds.
Fix at Last Meas-
During the test, all outputs will report the last measured value of their
ured Value
assigned process variable. The test will run for approximately
140 seconds.
Fix at Fault
During the test, all outputs will go to their configured fault action. The
test will run for approximately 140 seconds.
The test starts immediately.
Wait for the test to complete.
Tip
At any time during the process, you can abort the test. If the outputs were fixed, they will
return to normal behavior.
When SMV is licensed, results for the test are stored in the transmitter memory,
along with results for tests performed with any other tool. These results are also
stored in the ProLink III database. You can view and use these results in any tool-
based trending and reporting functions.
When SMV is not licensed, results from previous tests are saved in a database, but
not accessible. A Pass/Fail indication is all that is provided for the current test.
Section 12.1
if you have not done so already.