Configure Process Variable Fault Action - Emerson Micro Motion 5700 Configuration And Use Manual

Transmitters with configurable outputs
Hide thumbs Also See for Micro Motion 5700:
Table of Contents

Advertisement

Configure advanced options for process measurement
March 2019
Field Communicator
Not available
The transmitter can write the current value of four totalizers or inventories to a log, at user-specified intervals.
You can generate a log file from this data for viewing and analysis.
Procedure
1. Specify the date on which totalizer logging will begin.
You must specify a future date. If you try to specify the current date, the transmitter will reject the
setting.
2. Specify the time at which totalizer logging will begin.
3. Specify the number of hours between records.
4. Select up to four totalizers or inventories to be logged.

6.7 Configure Process Variable Fault Action

Display
Menu > Configuration > Alert Setup > Output Fault Actions
ProLink III
Device Tools > Configuration > Fault Processing
Field Communicator
Configure > Alert Setup > Output Fault Actions > Channel E > Process Var Fault Action
Process Variable Fault Action specifies the values that will be reported via the display and digital
communications if the device encounters a fault condition. The values are also sent to the outputs for
processing against their configured fault actions.
Procedure
Set Process Variable Fault Action as desired.
Default: None
Restriction
If you set Process Variable Fault Action to NAN, you cannot set mA Output Fault Action or Frequency
Output Fault Action to None. If you try to do this, the transmitter will not accept the configuration.
Important
If you want the mA Output to continue reporting process data during fault conditions, you must set both
Process Variable Fault Action and mA Output Fault Action to None. If mA Output Fault Action is set to
None and Process Variable Fault Action is set to any other option, the mA Output will produce the signal
associated with the selection.
If you want the Frequency Output to continue reporting process data during fault conditions, you must set
both Process Variable Fault Action and Frequency Output Fault Action to None. If Frequency Output
Fault Action is set to None and Process Variable Fault Action is set to any other option, the Frequency
Output will produce the signal associated with the selection.
114
Micro Motion Model 5700 Transmitters with Configurable Outputs
Configuration and Use Manual
MMI-20025166

Advertisement

Table of Contents
loading

Table of Contents