Integrate the meter with the control system
Example: Damping interaction
Configuration:
Result: A change in the mass flow rate will be reflected in the mA Output over a time
period that is greater than 3 seconds. The exact time period is calculated by the
transmitter according to internal algorithms which are not configurable.
6.2.5
Configure mA Output Fault Action and mA Output Fault
Level
ProLink III
Field Communicator Configure > Manual Setup > Inputs/Outputs > mA Output > mA Fault Settings
Overview
mA Output Fault Action controls the behavior of the mA Output if the transmitter
encounters an internal fault condition.
Note
For some faults only: If Fault Timeout is set to a non-zero value, the transmitter will not implement
the fault action until the timeout has elapsed.
Procedure
1.
2.
68
Flow Damping = 1 second
mA Output Source = Mass Flow Rate
mA Output Damping = 2 seconds
Device Tools > Configuration > Fault Processing
Set mA Output Fault Action to the desired value.
The default setting is Downscale.
Restriction
If Digital Communications Fault Action is set to NAN (not a number), you cannot set mA
Output Fault Action or Frequency Output Fault Action to None. If you try to do this, the
transmitter will not accept the configuration.
If you set mA Output Fault Action to Upscale or Downscale, set mA Output Fault Level
as desired.