9
Complete the configuration
Topics covered in this chapter:
•
•
•
9.1
Test or tune the system using sensor
simulation
Display
ProLink III
Web browser
Overview
Use sensor simulation to test the system's response to a variety of process conditions,
including boundary conditions, problem conditions, or alert conditions, or to tune the
loop.
Prerequisites
Before enabling sensor simulation, ensure that your process can tolerate the effects of the
simulated process values.
Procedure
1.
2.
3.
Configuration and Use Manual
Test or tune the system using sensor simulation
Save the transmitter configuration to a backup file
Enable or disable software write‐protection
Menu > Service Tools > Sensor Simulation > Simulate Sensor
Device Tools > Diagnostics > Testing > Sensor Simulation
Service Tools > Simulation > Sensor Simulation
Enable sensor simulation.
For mass flow, set Wave Form as desired and enter the required values.
Option
Fixed
Sawtooth
Sine
For density, set Wave Form as desired and enter the required values.
Required values
Fixed Value
Period
Minimum
Maximum
Period
Minimum
Maximum
Complete the configuration
141