10.Multi-Hold Mode

10-3-9. Four Types of Inflection Point Hold

Detection starts when the H/M signal is input and the indicated value crosses over the
Hold Start Level. Detection is performed while the H/M signal is ON. The COMPLETE
output is made immediately when there is a minute slope. Therefore, if the Judgment
output is taken in immediately after the COMPLETE output is made, correct results may
not be able to be obtained as is the case with the peak hold.
Take in the Judgment output after determination of the hold by turning off the H/M
signal. The hold can be cancelled by turning on the T/H signal as a reset signal.
Four types of Inflection Point Hold
Each inflection point hold is explained by the method in "16-2-12. Minimum Slope
Detection Value / Slope Detection Interval A / Slope Detection Interval B / Preliminary
Slope Detection Point" P118. (Point a is held as an inflection point when the amount of
change D exceeds the set "Minimum Slope Detection Value".
Inflection Point Hold A
Inflection Point Hold C
Slope Detection Intervals
57
Load
Inflection Point Hold D
+
Inflection Point Hold A
Slope change point
a
A
B
Slope Detection Intervals
Preliminary Slope
Detection Point
D
Slope change point
C
a
C
A
B
Inflection Point Hold B
+
+
Inflection Point Hold C
+
Inflection Point Hold B
D
Slope change point
C
C
Inflection Point Hold D
C
C
D
Preliminary Slope
detection point
Time
Slope Detection
Intervals
A
B
C
C
a
D
Preliminary Slope
detection point
Slope Detection
Intervals
A
B
a
Slope change point
Preliminary Slope
Detection Point