4. Methods of Connection

4-1. Connection to the Cage Clamp Type Terminal Block

Connect to the cage clamp type terminal block by using the attached mini-screwdriver.
1. Peel the sheath of the wire to be connected 5 ~ 6mm, and twist the end to such an
2. Insert the screwdriver firmly into the hole on the right-hand side while pushing it up
3. Insert the wire into the hole on the left-hand side so as not to loosen the end.
4. Withdraw the screwdriver.
5. Lightly pull the wire to check that it is clamped securely.
Request
extent so that it will not become loose.
5 ~ 6mm
slightly.
・ Wires connectable to the cage clamp type terminal block are
0.2 ~ 2.5mm2.
・ Do not attach crimp contacts to the ends of wires, or solder them.
・ When connecting two or more wires, twist them beforehand.
4.Methods of Connection