High Limit / Low Limit / Hi-Hi/Lo-Lo Mode / Hi-Hi Limit / Lo-Lo Limit - Unipulse f395 Operation Manual

Dynamic force processor
Table of Contents

Advertisement

16.Code Setting
・ The hold point prior to switching of the operation ch is taken as a reference value, from
・ The reference value=0 at sampling-start time.
・ When sampling ends, the relative values on the last operation ch are maintained.
・ The relative value is not updated by hold / hold cancel on the same ch.
・ Graphs of high and low limits are also displayed in relative values.

16-2-7. High Limit / Low Limit / HI-HI/LO-LO Mode / HI-HI Limit / LO-LO Limit

The High Limit output is turned on when the indicated value exceeds the set High Limit,
and the Low Limit output is turned on when the indicated value falls short of the set Low
Limit by this function. The HI-HI Limit and LO-LO Limit can also be set in a like
manner. While Judgments on High and Low Limits are made only with respect to the
indicated value, either Judgments Relative to the indicated value (Hold Value) or sensor
input value (Sampling Value) can be set on HI-HI and LO-LO Limits under HI-HI/LO-
LO Mode. Also, the set values of High and Low Limits on the operation ch in current use
are displayed on the main screen. (See "2-1-1. Touch Panel Type Color Liquid Crystal
Display" P7.)
<High/Low Limit output conditions>
High Limit / Low Limit / HI-HI Limit / LO-LO Limit
HI-HI/LO-LO Mode
* In the Waveform Comparison / Waveform and Displacement Comparison mode, High
109
which to the set values of high and low limits is taken as an OK judgment area.
High Limit output: Indicated value > Set value of High Limit
Low Limit output: Indicated value < Set value of Low Limit
HI-HI Limit output LO-LO Limit output:
Comparison value > Set value of HI-HI Limit
Comparison value < Set value of LO-LO Limit
* For HI-HI Limit output / LO-LO Limit output, if the HI-HI/LO-
LO Mode setting is "Hold ":
and if the HI-HI/LO-LO Mode setting is "Sample":
Setting range: -9999 ~ +9999 (Not including the decimal point.)
Setting item: Hold / Sample
MODE
Code Set
and Low Limits are not displayed.
Comparison value = Indicated value,
Comparison value = Sensor input value
Judgment:
HH/LL Mode / HI-HI Limit /
LO-LO Limit
HI Limit / LO Limit /

Hide quick links: