17.7

Use example (utilization of clock data)

Clock data built in to the GOT can be transferred to a data register in the PLC for utilization
while a specified bit device is ON. The clock data is stored in the following registers. However,
only GT Designer can handle these registers. In the case of DU/WIN-E, it is available for V2.50
or later.
GD0: Current time (second)
GD2: Current time (hour)
GD4: Current time (month)
GD6: Current time (day of week)
Example: When the clock data (year, month, day, hour, minute and second) is transferred to
register D100 in the PLC every 30 seconds while M10 is ON
Select "Observe Status" in the screen creation software.
1) Select "Project", and set the cycle to 30 seconds.
2) Set the trigger 1 to "M10, ON".
3) Select "Word Set (16-bit)" as the operation, and set the number of points to "7".
4) Set "Storing Device" to "D100", "Fixed" to "0" and "Indirect Device" to "GD0".
5) Set the transfer method to "BMOV".
When this data is transferred to the F940GOT, the current time is stored in D100 at every 30
seconds while M100 is ON.
GD1: Current time (minute)
GD3: Current time (day)
GD5: Current time (year)